When Should I Choose Armoured Cable?

Choose armoured cable when the route exposes the cable to impact, crushing, pulling stress or direct burial, and local rules do not accept conduit or guarded tray instead. Armour adds mechanical protection only: it does not make a cable waterproof or fireproof. The armour type must also match whether the circuit is multicore or single-core AC.

When does a project need armoured cable?

Armoured cable is usually specified where the cable faces a mechanical risk that the outer sheath alone cannot handle. Typical cases include:

  • Direct burial in soil, where stones, digging tools and ground movement can damage the cable.
  • Industrial plants, where vehicles, equipment and falling objects can strike the route.
  • Tunnels and cable trenches, where the cable is exposed to impact or must be pulled into place.
  • Routes where the cable is exposed to pulling stress during installation or later movement.

Conduit or guarded tray may be an alternative in many places. Whether it is allowed depends on local rules, so check those rules before the armour is specified rather than after the order is placed.

Which armour type fits a multicore or single-core circuit?

Armour type follows the cable construction as well as the site. Steel wire armour (SWA) is widely used on multicore cables where tensile and mechanical protection are needed. Steel tape armour gives radial protection in many fixed installations.

Single-core AC cable needs more care. Steel around one AC conductor causes magnetic losses (eddy current and hysteresis), which heat the cable. For that reason single-core AC cable is normally armoured with non-magnetic aluminium wire armour (AWA). Sheath bonding for single-core cables is a separate design question, covered in the single-core sheath bonding guide.

Two British standards are often quoted for this construction. BS 5467 covers single-core AWA and multicore SWA cables for 0.6/1 kV use. BS 6724 covers the LSZH-sheathed armoured equivalent. Confirm which standard and construction your project specifies before ordering.

How do the situation and armour choice fit together?

The table below gives a starting point for the buyer's specification. It does not replace the cable standard or the project's electrical design.

SituationArmour choiceReason
Multicore power cable, direct burialSteel wire armour (SWA) with an intact outer sheathTensile and mechanical protection
Single-core AC circuitNon-magnetic aluminium wire armour (AWA)Steel around one AC conductor causes magnetic losses and heating
Fixed installation needing radial protectionSteel tape armourRadial protection in many fixed installations
Wet or corrosive groundArmour plus separate water protection and a sound outer sheathArmour is not the water barrier, and a damaged sheath exposes steel to corrosion
No mechanical risk on the routeUnarmoured cable may be sufficientArmour adds cost and weight, so confirm the need with the installation rules

These are starting points only. The cable standard edition and the manufacturer datasheet decide the final armour construction.

Does armour make the cable waterproof or fireproof?

No. Armour is not the water barrier. Moisture performance comes from the bedding, the sheath, the water-blocking layers and the installation drainage. A damaged outer sheath can expose the steel to corrosion, and an armoured cable can still fail after water enters. Specify water protection separately, and treat drainage, bedding, joints and sheath integrity as part of the underground design.

Fire performance is a separate requirement. If the project needs low smoke or halogen-free behaviour, specify it with the sheath material, as explained in the flame retardant and LSZH guide.

How do glands, earthing and bonding work with armour?

Cable glands must fit both the cable diameter and the armour type. IEC 62444 covers cable glands for electrical installations, and hazardous-area glands also follow the IEC 60079 series. Check the gland IP rating against the site. IP66 means dust-tight and protected against powerful water jets, and IP68 means continuous immersion under conditions the manufacturer states (IEC 60529). Gland selection is covered in more detail in the cable gland selection guide.

Armour continuity, bonding and earth-fault performance must be verified. Do not assume the armour alone is an adequate protective conductor without calculation. Armour selection and earthing must be coordinated with the electrical protection design from the start.

What to confirm before ordering

  1. The mechanical risk: direct burial, impact, crushing or tensile pulling.
  2. Whether the circuit is single-core AC or multicore, which decides between SWA, AWA and steel tape armour.
  3. Water and corrosion exposure, and whether a separate water protection layer is needed.
  4. The required armour construction and the standard edition, such as BS 5467 or BS 6724.
  5. Whether a low-smoke or halogen-free sheath is required.
  6. Gland type, IP rating, and the bonding and earthing method.
  7. Outer diameter and minimum bending radius, taken from the manufacturer datasheet.

Frequently asked questions

Does armoured cable have to be waterproof?

No. Armour is not a water barrier. Moisture protection comes from the bedding, sheath and water-blocking layers, and it is specified separately from the armour.

Why is single-core AC cable armoured with aluminium instead of steel?

Steel around a single AC conductor causes magnetic losses and heating. Non-magnetic aluminium wire armour (AWA) avoids this problem.

Can the armour be used as the protective earth conductor?

Not without calculation. Armour continuity, bonding and earth-fault performance must be verified before the armour is relied on as a protective conductor.

What IP rating should an armoured cable gland have?

Match the gland IP rating to the site conditions. IP66 covers dust-tight and powerful water jet protection, while IP68 covers continuous immersion under conditions the manufacturer states.

Can conduit or guarded tray replace armour?

In many places they can be an alternative, depending on local rules. Check the installation rules before deciding, because the choice affects the cable specification.

Which standard covers armoured cable with a low-smoke sheath?

BS 6724 covers the LSZH-sheathed armoured equivalent of the BS 5467 construction. Confirm the edition your project requires.

References

  • Prysmian, A guide to armoured cableSupports the SWA and AWA armour choices, the non-magnetic armour rule for single-core AC cable, and the BS 5467 and BS 6724 constructions.
  • IEC 62444 standard sampleSupports the statement that cable glands for electrical installations are covered by IEC 62444.
  • IP code overviewSupports the meaning of IP66 and IP68 in the gland rating discussion.

Related cable products

Continue reading

Need a project quotation?

Send the cable model, voltage, conductor size, quantity, installation conditions and destination by WhatsApp or email.

Discuss on WhatsApp
WhatsApp