Cable Knowledge
What Standards and Test Reports Can Cable Buyers Request?
A cable order should tie the product designation to a named construction standard and a test plan. Buyers can request routine test reports for the supplied lengths, sample and type test reports for the same construction, and documents that show the manufacturer, the standard edition and the laboratory involved. Each document proves something different, and a genuine report only applies if it matches the exact cable being bought.
Which standards does a cable order need to reference?
A cable may reference a construction standard plus separate test standards for conductor resistance, flame propagation, and smoke or halogen gases. The construction standard depends on the voltage class and the product. IEC 60502-1 is commonly used for certain extruded power cables, such as 0.6/1 kV cables. For medium voltage, IEC 60502-2 covers extruded-insulation cables from 6 kV (Um 7.2 kV) to 30 kV (Um 36 kV), and IEC 60840 covers the range above 30 kV up to 150 kV (Um 170 kV). Other cable families use different standards, so the standard for the product being bought should be named in the quotation rather than assumed.
Conductor construction and resistance are covered by IEC 60228. As an example, the standard gives a maximum DC resistance at 20 °C of 7.41 Ω/km for a 2.5 mm² plain copper class 1 or class 2 conductor. Tinned conductors have slightly higher limits, so the conductor type in the offer should match the limit being checked.
What do routine, sample and type tests each prove?
Routine tests are performed on manufactured lengths as the applicable standard requires. Sample tests examine selected production samples or check dimensions. Type tests demonstrate that a cable design can meet the specified performance requirements. Typical routine checks include conductor resistance and voltage testing, while sample checks often cover dimensional verification.
For 0.6/1 kV cables, datasheets commonly list a routine voltage test of 3.5 kV AC for 5 minutes, based on the IEC 60502-1 routine test. For medium-voltage cables, a routine partial-discharge limit commonly cited for IEC 60502-2 cables is no discharge above 10 pC at 1.73 U0. The medium-voltage routine AC withstand test voltage and duration depend on the cable and the standard edition, so take those values from the manufacturer's datasheet.
| Document | What it proves | What to check on it |
|---|---|---|
| Routine test report | The tests required by the standard were run on the manufactured lengths | Cable designation, lengths tested, result and acceptance criteria |
| Sample test report | Selected production samples were checked for dimensions and the sample tests specified | Sample identification, test date and the test clauses used |
| Type test report | A cable design can meet the specified performance requirements | Construction, size range, materials and standard edition |
| Management-system certificate | The manufacturer's quality management system is certified | Certificate holder and scope, which does not certify an individual cable product |
| Third-party inspection report | An independent inspector checked the tests within the agreed scope | Inspection scope, tests covered and the date of inspection |
Check the sample description and the test date on every report, not only the result page.
What should a document review cover?
Before accepting any report, check the following details against the offer. Each item shows whether the report describes the cable being bought.
- Manufacturer and production site
- Cable designation and tested construction
- Standard edition and test clauses
- Sample identification and test date
- Result and acceptance criteria
- Laboratory or certification body status
Test scope is set by the standard and the project, so a complete review also confirms which tests were required and which were actually performed. For the wider inspection plan, see factory testing and inspection.
How do I check whether a report applies to my order?
Match the report's manufacturer, factory, cable construction, voltage, size range, material and standard edition to the product offered. A genuine report for a different construction may still be irrelevant to the purchase. Three habits help avoid this mistake:
- Read the sample description, not only the result page.
- Check the test date and the identity of the laboratory.
- Keep approved documents with the purchase record.
Does a management-system certificate cover my cable?
No. A management-system certificate shows that the manufacturer's quality system has been certified. It does not certify an individual cable product, so the routine test report and the relevant type-test evidence are still needed for the cable being ordered.
Which fire tests are worth requesting?
Fire performance is covered by several separate standards, and the required values depend on the project. IEC 60332-1-2 is a flame test on a single vertical cable. IEC 60754-1 measures halogen acid gas, where 0.5 % or less is a commonly used LSZH acceptance value. IEC 61034-2 sets a minimum light transmittance of 60 %, which is commonly used to classify low smoke, and some sectors, such as rolling stock, require higher values. Ask the supplier which of these tests the offered construction has been subjected to, and for what results.
What to confirm before ordering
- Applicable product standard and test standards, with the edition named
- Inspection and test plan for the order
- Required routine test report for the lengths supplied
- Required type-test evidence matching the construction and size range
- Third-party inspection scope, if an independent inspection is required
- Document language and submission schedule
- Fire-performance test standard and acceptance value required by the project
Frequently asked questions
What is the difference between routine, sample and type tests?
Routine tests are run on manufactured lengths, sample tests check selected production samples and dimensions, and type tests show that a cable design meets the specified performance requirements.
Is a management-system certificate the same as a product certificate?
No. A management-system certificate does not certify an individual cable product, so ask for the routine and type-test reports for the cable offered.
Can a type test report for a similar cable be used?
Only if the manufacturer, factory, construction, voltage, size range, material and standard edition match the order. A report for a different construction may be irrelevant.
Which standard covers medium-voltage power cable?
IEC 60502-2 covers extruded-insulation cables from 6 kV (Um 7.2 kV) to 30 kV (Um 36 kV), and IEC 60840 covers the range above 30 kV up to 150 kV (Um 170 kV).
What routine voltage test should a 0.6/1 kV cable pass?
Datasheets commonly list 3.5 kV AC for 5 minutes, based on the IEC 60502-1 routine test. Confirm the value against the standard edition named in the offer.
Should I ask for the medium-voltage withstand test value?
Yes. The value depends on the cable and the standard edition, so take it from the manufacturer's datasheet rather than from a general figure.
References
- IEC 60228: Conductors of insulated cablesReference for conductor construction and resistance requirements.
- IEC: International StandardsOfficial IEC standards catalogue for checking the required edition and scope of IEC 60502-1.
- IEC 60502-2 (IEC Webstore)Scope of IEC 60502-2: extruded-insulation cables from 6 kV to 30 kV.
- CIGRE US National Committee paper on cable system testingSource for the commonly cited routine partial-discharge limit of 10 pC at 1.73 U0.
Related cable products
- XLPE Insulated Power Cable
- PVC Insulated Power Cable
- Control Cable
- Rubber Flexible Cable
- Welding Cable
- Solar PV Cable
Continue reading
- How Do Copper Price and Quantity Affect Cable Price?
- How to Choose Solar PV Cable for a Photovoltaic Project
- How to Choose Rubber Flexible Cable or Welding Cable
- What Should Be Checked Before Shipping Cable Orders?
Send the cable model, voltage, conductor size, quantity, installation conditions and destination by WhatsApp or email.
Discuss on WhatsApp