How to Choose Solar PV Cable for a Photovoltaic Project
A solar PV string cable has to carry DC power outdoors for many years, so choose it by checking three things together: the maximum system DC voltage and design current, the conductor temperature in the hottest credible operating condition, and a construction built to IEC 62930 or EN 50618. The connectors and the way the cable is supported matter as much as the cable itself. Confirm these points against the product datasheet before you place an order.
What does a PV string cable have to withstand?
A PV string cable runs outdoors for long periods under DC voltage, sunlight and temperature cycling. Rooftops and solar farms expose it to UV, ozone, heat, cold, water and movement, and these conditions act together. A cable that meets only the electrical rating can still fail early if its sheath is not suited to the site.
Most decisions in this guide follow from one question: what is the hottest condition the cable will see, and for how long will it stay there? Answer that first, and the rest of the selection becomes a matter of matching ratings.
How do you size a PV string cable?
Size the conductor from the design current, and apply the multipliers, grouping and ambient temperature prescribed by the project rules. Long strings may need a larger conductor to control voltage drop and energy loss, because a larger conductor reduces voltage drop along the same route. The voltage drop check should be run on the full route length, not on a single panel.
Correction factors multiply: the tabulated current rating is multiplied by the ambient temperature factor, the grouping factor and any other factor that applies. For PV cable, take the current ratings and correction factors from the PV cable manufacturer's datasheet or the rating tables that accompany the cable standard, because they are based on the cable's own temperature limits rather than on general-purpose cable tables. The project's PV design rules set the ambient temperature and grouping for the real installation.
Current capacity in amperes depends on installation method and must come from the applicable tables or the manufacturer. The ampacity and derating guide explains how the correction factors are applied.
What do the PV cable ratings mean?
IEC 62930 and EN 50618 set the core ratings for cable used with photovoltaic systems. The table below summarises the values these standards give for a typical PV cable such as H1Z2Z2-K, with the check to make for each one. Each value is a basis for comparison, so the product datasheet for your exact product code still governs.
| Requirement | Basis | What to check |
|---|---|---|
| Rated voltage | 1.5 kV DC (IEC 62930 / EN 50618) | Confirm the rating covers the design DC voltage of the string |
| Permissible system voltage | 1.8 kV, stated on many manufacturer datasheets | Compare this figure with your design maximum; it is separate from the 1.5 kV rating |
| Normal operating temperature | 90 °C maximum continuous conductor temperature (IEC 62930 / EN 50618) | Check that the hottest credible conductor temperature stays below this limit |
| Short-term high temperature | 120 °C conductor temperature, limited to 20,000 h in total (IEC 62930 / EN 50618) | Ask the supplier to confirm this rating and the total hour limit in writing |
| Expected service life | At least 25 years under the standard's normal conditions (IEC 62930 / EN 50618) | Ask which operating conditions the life claim assumes |
| Conductor and construction | Single-core, cross-linked insulation and sheath, tinned flexible copper (EN 50618) | Check conductor material, tinning, insulation and sheath type on the datasheet |
Values are summarised from IEC 62930 and EN 50618 as cited in manufacturer datasheets. Check the current edition of the standard and the product datasheet before you rely on them.
Which standard should you specify on the order?
IEC 62930 is the international reference for electric cables used with photovoltaic systems, and EN 50618 is cited for the same kind of cable. Specify the standard by name on the purchase order, together with the product designation such as H1Z2Z2-K. Projects may also require other regional standards or approvals, so confirm these before comparing prices.
Confirm conductor, insulation, sheath, temperature and voltage ratings together. A cable can meet one requirement and still fall short on another, and a supplier answer that covers only one of them is not enough to confirm the product.
How do connectors and crimping affect the circuit?
Use compatible connectors, approved tools and a documented crimping procedure. Mixing connector families or poor crimping can create high-resistance joints, and such joints can overheat even when the cable itself is correctly sized. Increasing the conductor size does not fix a poor joint.
- Confirm that the connector is listed as compatible with the cable you are buying.
- Avoid mixed connector families unless the design explicitly approves them.
- Require the crimp tool and procedure named by the connector maker, and keep a record of them.
How should PV cable be routed and supported?
Support the cable away from sharp edges and standing water. Avoid loose loops that rub on roofing or lie on the ground, because movement and abrasion add stress to the sheath and to the connector exits. Choose a sheath and armour that suit UV and weather exposure at the site, and state this exposure to the supplier when you order.
The minimum bending radius depends on the cable construction and the edition of the standard, and published values do not agree. Take the figure from the manufacturer's datasheet and apply it at every bend, including the bends at the connectors. PV circuit design and installation must follow the applicable local electrical and fire rules.
What to confirm before ordering
- Maximum system DC voltage and design current, with the hottest credible conductor temperature.
- Route length and the voltage drop target for the string.
- Cable standard (IEC 62930 or EN 50618) and any regional standards or approvals required.
- UV, ozone, water and mechanical exposure at the installation site.
- Connector family, compatible crimp tools and the crimping procedure.
- Colour, marking, packaging and quantity, with the datasheet for the exact product code.
Frequently asked questions
Can a cable rated 1.5 kV DC be used for any PV system voltage?
No. Compare your design maximum system DC voltage with both the 1.5 kV DC rating and the permissible system voltage on the datasheet, which many manufacturers state as 1.8 kV.
What does IEC 62930 cover?
IEC 62930 is the international reference for electric cables used with photovoltaic systems. EN 50618 is cited for the same kind of cable, and projects may need other regional approvals.
Is operation at 120 °C allowed for PV cable?
The standard allows operation at a 120 °C conductor temperature only for a limited total of 20,000 h. The normal continuous maximum conductor temperature is 90 °C.
Why might a long string need a larger conductor?
Voltage drop and energy loss grow with route length and current. A larger conductor reduces voltage drop, so it can be needed to meet the voltage drop target on a long run.
Can connectors from different families be mixed?
Only when the design or the connector maker explicitly approves it. Mixing families or poor crimping can create high-resistance joints.
What should I ask the supplier for before ordering?
Ask for the datasheet of the exact product code, the standard it is built to, the matching test report and the minimum bending radius. Ask for the conditions behind the expected service life as well.
References
- IEC 62930 sample document (iTeh Standards)Source for the IEC 62930 PV cable ratings summarised in the table above.
- Topcable TOPSOLAR PV H1Z2Z2-K datasheetExample datasheet showing the permissible system voltage and the cable construction.
Related cable products
- XLPE Insulated Power Cable
- PVC Insulated Power Cable
- Control Cable
- Rubber Flexible Cable
- Welding Cable
- Solar PV Cable
Continue reading
- How to Choose Rubber Flexible Cable or Welding Cable
- What Should Be Checked Before Shipping Cable Orders?
- Cable Ampacity and Derating Factors Explained
- How to Check Cable Voltage Drop
Send the cable model, voltage, conductor size, quantity, installation conditions and destination by WhatsApp or email.
Discuss on WhatsApp