Shielded Cable or Unshielded Cable: How to Decide?

Use a shielded cable when the signal is sensitive to electrical noise and the route passes motors, variable-frequency drives, contactors or other noise sources. An unshielded cable is usually enough when the signal is robust, the run is short and the surroundings are quiet. A shield only helps when it is selected, terminated and bonded as part of a complete system, because a metal layer without a grounding plan can add little benefit and can create unwanted current paths.

When does a shield actually help?

Variable-frequency drives, motors, contactors, transformers and radio transmitters can all couple noise into control and instrumentation circuits. Coupling becomes more likely when sensitive conductors run in long parallel with a noisy cable, or when the loop formed by the signal wires encloses a large area. Long parallel runs and large loop areas both increase susceptibility.

A shield does not replace good routing. Keeping loop areas small and routing sensitive pairs away from power circuits is usually the first and cheapest step. A shield is then added where the remaining risk justifies the extra cost and termination work.

A shield is most useful when the signal is low level, when it carries high-frequency content, or when the cable must run beside equipment that switches quickly. A slow, high-level signal over a short run inside a quiet panel may need little or no shielding.

What is the difference between foil, braid and combined shields?

Each shield construction has a typical use. The main options are listed below.

  • Foil shield: high coverage and compact construction, often supplied with a drain wire for termination.
  • Copper braid: mechanically durable, and suitable where the cable must stay flexible.
  • Combined foil and braid: addresses a broader range of conditions, but adds diameter and cost.

Foil and braid behave differently at high frequency. Braid generally gives lower impedance at many frequencies, while foil gives high coverage in a thin layer. Neither is better in every case. The right choice depends on the frequency range, the mechanical duty of the cable and the termination that can actually be achieved in the installation.

Should the shield be grounded at one end or both ends?

Single-end or both-end termination depends on the frequency, the circuit design, the equipotential bonding and the manufacturer's instructions. There is no universal rule. The method should be confirmed with the equipment designer or the cable manufacturer before the cable is installed.

At high frequency, a shield generally works best with a low-impedance circumferential termination, meaning the shield is bonded all the way around the cable at the gland or connector. A long, thin pigtail, which is a wire lead from the shield to earth, adds impedance at high frequency and can make an otherwise good shield perform poorly.

The bonding arrangement also has to fit the plant earthing system. Two earth points that sit at different potentials can drive current through a shield that is bonded at both ends, so the bonding design should be checked against the site layout rather than chosen by habit.

Which applications usually need a shield?

The table below is a starting point for discussion. It does not replace the equipment manufacturer's requirements or a site assessment of the electrical noise environment.

SituationShield usually advised?What to check
Analogue instrument signal beside a driveYesUse a shield with low-impedance termination and keep the run apart from drive output cables.
Serial or fieldbus communication in a noisy plantUsually yesConfirm the protocol's cable requirements and the shield termination method.
Short control run inside a quiet panelOften not neededRouting and separation often solve the problem; a shield adds cost and termination work.
Motor cable fed by a variable-frequency driveUse the drive maker's recommended cableSymmetrical construction with an overall shield bonded at both ends is commonly used.
Flexible cable in a cable carrierShield where the flexing duty requires itCheck the flexing and bending limits in the datasheet before choosing a braided or combined shield.
Long parallel run beside power cablesShielded, with physical separationSeparation and shielding work together; neither replaces the other.

Requirements vary by equipment and site. Confirm the final choice against the datasheet and the installer's specification. For shielded signal cables, see the computer shielded cable range.

What about cables feeding variable-frequency drives?

Drives switch quickly and can produce common-mode current, which can cause EMC problems on nearby control and communication circuits. Symmetrical cable construction, with three phase conductors and three symmetrically placed earth conductors, is used together with an overall shield bonded at both ends to reduce common-mode current and EMC problems.

A symmetrical shielded cable does not solve every drive problem by itself. Reflected-wave overvoltage at the motor is a separate issue. It is addressed by cable length limits, dv/dt or sine filters, and motors with insulation suited to inverter duty. For a fuller discussion, see the VFD motor cable guide.

What to confirm before ordering

  1. The signal or protocol to be carried, and how sensitive it is to noise.
  2. The operating voltage and the frequency range of the signal.
  3. Nearby power, motor and variable-frequency drive circuits, and the separation planned between them.
  4. Cable length, routing, and any movement or flexing in service.
  5. Required pairs, pair twisting, and whether individual or overall shields are needed.
  6. Shield type (foil, braid or combined), the coverage required, and any capacitance limits.
  7. The termination method at both ends, including the gland and connector arrangement.
  8. Environmental requirements and the datasheet values the supplier will guarantee.

Frequently asked questions

Do I always need a shielded cable for a control signal?

No. A shield is needed when noise is likely to couple into the signal, such as near drives, motors or contactors. Quiet, short runs with good separation often do not need one.

Should the shield be earthed at one end or both ends?

It depends on the frequency, the circuit design, the bonding arrangement and the manufacturer's instructions, so there is no universal answer. Confirm the method before the cable is ordered or installed.

Is braid better than foil?

Neither is better in every case. Braid is more robust and usually has lower impedance at many frequencies, while foil gives high coverage in a compact cable.

Does a shielded cable solve all drive problems?

No. A symmetrical shielded cable reduces common-mode current, but reflected-wave overvoltage at the motor also needs cable length limits, dv/dt or sine filters, or suitable motor insulation.

What should I tell the supplier when asking for a shielded cable?

Give the signal type, the operating voltage and frequency range, the nearby power or drive circuits, and the cable length and movement. State the shield type and the termination method you need.