Control Cable vs Instrumentation Cable

Control cable and instrumentation cable can look alike, but they are built for different circuit functions. Control cable normally carries discrete control signals, relay and interlock circuits, actuator circuits and auxiliary power, often as a multicore cable. Instrumentation cable is designed around low-level analogue or digital signals from sensors and transmitters, usually as twisted pairs or triads with screens chosen to limit noise and coupling.

What is the difference between control cable and instrumentation cable?

The difference starts with the circuit. Control cable carries commands and status between a control panel and field equipment. Typical uses are relay outputs, interlock circuits, actuator circuits and auxiliary power for control equipment.

Instrumentation cable is selected around the signal. Sensors and transmitters produce low-level analogue or digital signals that are easily disturbed by electrical noise. For that reason the cable is normally built with twisted pairs or triads, and the screens are chosen to protect each signal from its neighbours and from outside interference. The main question is what the circuit must carry and how much interference it can tolerate, not only how much current it draws.

The table below summarises the main differences.

FeatureControl cableInstrumentation cable
Typical signalsDiscrete control, relay, interlock, actuator and auxiliary power circuitsLow-level analogue or digital signals from sensors, transmitters and communication links
Usual constructionMulticore cable with several cores in one jacketTwisted pairs or triads, sometimes multicore with pair screens
ScreeningOverall screen where the installation needs oneIndividual pair screens, an overall screen, or a combination of both
Electrical parametersUsually checked against the load and voltage of each circuitCapacitance, impedance and pair balance may matter for analogue, pulse or communication circuits
Main selection riskMixing circuits that need different protection on one generic cableChoosing by conductor cross-section alone
Installation noteKeep apart from power and VFD cables as the design requiresKeep sensitive pairs away from power and VFD cables and maintain shield continuity

Construction and screening options vary by manufacturer and by the signal-system design. Take the exact electrical values from the manufacturer's datasheet.

How does a loop schedule decide which cable you need?

A loop schedule lists each field device and the circuit that connects it to the control system. Reading the schedule shows which circuits are analogue pairs, which are digital communication lines, which are relay outputs and which carry auxiliary power.

The common mistake is to buy one generic multicore cable for the whole job. Circuits with different signal types need different shielding and electrical properties. If they share one cable without separation, the sensitive pairs may lack the screening they need, and the cable may not terminate cleanly at the marshalling points.

  • Group circuits by signal family, for example discrete, analogue, digital communication and auxiliary power.
  • Record the signal type and the circuit voltage for each group.
  • Decide the pair, triad or multicore arrangement for each group.
  • Note any intrinsic-safety or grounding requirement that applies to a group.

Which screen arrangement suits your signals?

Screen options include overall foil, individual pair screens, braid, or combinations of these. Individual screens reduce coupling between pairs, which matters where neighbouring signals could interfere with each other. An overall screen addresses interference coming from outside the cable. Many instrumentation designs use both, but the choice depends on the signal and the environment.

A screen only works if it is continuous through the cable, the gland and the termination. A break at the gland or a poor earth connection can leave the signal unprotected even when the cable itself is correctly specified.

Which electrical parameters matter besides conductor size?

For analogue, pulse or communication circuits, capacitance, impedance and pair balance may matter. These properties are not described by conductor cross-section, so a cable chosen only by size can perform poorly on a sensitive circuit. Long signal runs make capacitance more significant, because the total capacitance grows with cable length.

Ask the supplier for the capacitance, impedance and pair balance values on the datasheet, and check them against what the receiving device requires. These values depend on the construction, so they should be taken from the manufacturer's datasheet rather than estimated from the conductor size.

Conductor class also matters where the cable must bend in service. Under IEC 60228, classes 1 and 2 are intended for fixed installation, while classes 5 and 6 are used for flexible cables and cords.

How should control and instrumentation cables be installed?

Separate sensitive signal circuits from power cables and from VFD cables. Where a crossing cannot be avoided, follow the separation rules in the design and installation specification rather than improvising on site.

Maintain shield continuity through the gland and the termination, and use approved gland and grounding methods. Where intrinsic-safety segregation applies, keep the circuits apart as the design requires. See cable gland selection for gland and earthing detail.

VFD cable is built differently. Symmetrical construction, with the phase conductors and earth conductors arranged symmetrically, and an overall shield bonded at both ends are used to reduce common-mode current and EMC problems. That is a property of the VFD cable itself. It does not remove the need to keep instrumentation pairs away from the drive wiring. For the motor side of a drive installation, see VFD motor cable guide.

Signal-system and hazardous-area requirements should be confirmed by the control-system designer before the cable is ordered.

What to confirm before ordering

  1. The signal type for each circuit, such as discrete, analogue, digital or communication.
  2. The circuit voltage, and whether auxiliary power is to be carried in the same cable.
  3. The number of pairs, triads or cores required, plus any spare cores the design calls for.
  4. Whether individual pair screens, an overall screen or both are required.
  5. Capacitance, impedance and pair balance limits for long or sensitive signal runs.
  6. Fire and environmental requirements, including outdoor exposure and the fire performance class.
  7. The termination, gland and grounding plan agreed with the installer.
  8. Any intrinsic-safety or hazardous-area requirement, confirmed by the control-system designer.

Frequently asked questions

Can I use control cable for an analogue sensor signal?

Sometimes, but analogue signals on long runs or in noisy areas usually need instrumentation construction with twisted pairs and suitable screening. Confirm with the control-system designer which circuits need which cable.

Does every instrumentation cable need a screen?

Not every circuit needs a screen, but the designer should decide based on the signal and the environment. Individual pair screens reduce coupling between pairs, while an overall screen addresses interference from outside the cable.

Why not buy one multicore cable for all circuits?

Circuits with different signal types need different shielding and electrical properties. A single generic cable can leave sensitive pairs without the screening they need.

What matters besides conductor size?

For analogue, pulse or communication circuits, capacitance, impedance and pair balance may matter. Take the exact values from the manufacturer's datasheet, because they depend on the construction.

Does conductor class matter for instrumentation cable?

Yes, if the cable must flex in service. Under IEC 60228, classes 1 and 2 suit fixed installation, while classes 5 and 6 suit flexible cables and cords.

Can instrumentation cable share a tray with power cables?

Only if the design allows it. Keep sensitive signal circuits separated from power and VFD cables and follow the separation rules in the installation specification.